CENTRIFUGAL
FANS: Medium & large size
Capacity
upto 260 m^3/sec.
corresponding static pressure upto 600 mm wcl,
Maximum temp. 400 Deg.C
Static
pressures upto 3400 mm wcl in a single stage for capacity
upto 12 m^3/sec.,
maximum temp. 150 Deg. C
|
|
| |
|
|
IMPELLERS
Backward
curved with aerofoil blades
Backward
curved laminar blades
Forward
curved blades
Forward
curved radial tipped blades
Radial
blades
Paddle
type blades
|
|
AXIAL
FLOW FANS: Impulse type and reaction type |
High
volume,low pressure
volume flow upto 260 m^3/sec,
pressure upto - 450 mm wcl
High
pressure fans: - Impeller directly mounted on motor
shaft for pressures upto 160 mm wcl.
For
higher pressures, 2 stage fans are available.
Fan
Controls:
Axial
inlet vane control for flow control pre vortex type for high
efficiency
Suction
chamber damper control for fans handling gases
Multiflap
outlet damper control, For low pressure fans and to be used
as additional control device
|
|
Control
by speed variation
1.Variable
frequency drive - most efficient
2.Slip
ring electric motors with variable speed system - Reasonable
efficiency
3.Steam
turbine drive - High efficiency
4.Speed
variation by hydraulic coupling - More helpful for starting,
pulse loads, low efficiency.
|
|
DUST
COLLECTORS
ISEL
Engineers have gained a wealth of process knowledge and detailed
information on the characteristics of gas and dust from various
industries. The in-depth knowledge gained from various performance
studies made at plant sites and engineering data available from
computer aided design packages has helped in selection and sizing
of suitable dust collectors.
A.CYCLONE
DUST COLLECTORS
The
high efficiency cyclones are manufactured in a wide variety
of construction to meet the various demands in the industry.
Wear
resistant material such as high hardness cast iron, Ni hard
are used for applications involving severe abrasion.
|
|
|
B.BAG
FILTER
ISEL
Bag filters are designed after obtaining complete information
on the application, operating conditions. The selection of the
filter cloth, type of cleaning system and over all construction
is to ensure specific requirement like flame proof construction,
explosion proof construction, leak proof construction etc.,
C.WET
SCRUBBERS
ISEL
mainly manufacturers two types of wet scrubbers
High
efficiency venturi scrubbers mostly with adjustable throat.
The venturi scrubber systems are some times arranged and designed
to include pre cooling system, spray cooling and dust collection
system - single stage or double stage venturi scrubbers
The
cyclone spray scrubber is utilised for applications requiring
minimum space and low pressure loss.
|
|
DAMPERS
& INLET VANE CONTROLS
ISEL
manufacturers the following types:
A.
AXIAL INLET VANE CONTROLS
a.Simple
ring and pin type
b.Costlier ball and socket joint connections
- type - more sensitive with minimum hysterisis
loss.
B.
MULTIFLAP DAMPERS
1.98%
leak proof for
a.control
application
b.open/close applications
2.100%
leak proof for special applications
|
|
C.
GUILLOTINE GATES:
100%
Leak proof of - Medium and large sizes
|
D.
SINGLE FLAP - CIRCULAR DAMPERS -
With gear box arrangement for diameters upto 1600 mm - 100 % Leak
Proof.
|
E.
SIMPLE 2 FLAP DAMPERS, SINGLE FLAP DAMPERS,
DIVERTING GATES etc.
|
|
SILENCERS
ISEL
mainly manufactures silencers for air/gas applications. The silencers
are designed knowing the application, noise level and noise spectrum.
|
 |
|
|